RELIABLE BY DESIGN
6U16KW-AC220V-R
Brand: INLANX
Description: INLANX-6U16KW-AC220V-R AC rack-mounted load bank is a high-power density rack-mounted test load equipment specially designed and developed for the 19-inch standard cabinet environment of IDC data center. 500W, 500W, 1KW, 2KW, 4KW, 4KW, 4KW step-by-step loading
Resistance, power rating, tolerance, TCR, package, lead length, mounting method, and labeling and packaging can all be customized.
Product series across the site can serve as alternatives to EBG, HVR, Vishay and other brands. Customers must verify samples and specifications before using replacement models in volume.
Total stock: 1,000
- Size
- 430*266*550 mm
- Rated power
- 16000 W
- Tolerance
- ±10%
- TCR
- 400 ppm
- Technology
- Metal tube / wirewound
- Series
- 6U16KW-AC220V-R AC rack load bank
- Brand
- INLANX
Description: INLANX-6U16KW-AC220V-R AC rack-mounted load bank is a high-power density rack-mounted test load equipment specially designed and developed for the 19-inch standard cabinet environment of IDC data center. 500W, 500W, 1KW, 2KW, 4KW, 4KW, 4KW step-by-step loading
Total stock: 1,000
Brand: INLANX
Product details
Product description
Our 6U16KW-AC220V-R rack load bank is designed for standard 19-inch rack environments in IDC data centers.
Technical features
- Alloy resistors provide stable power and low temperature drift; internal silicone cables withstand temperatures above 120℃.
- Loading is disabled until the fan starts. Overtemperature triggers audible and visual alarms and disconnects the load. Manual reset is permitted only after power-off is confirmed.
Technical specifications
| Rated voltage | AC220V / AC240V |
|---|---|
| Rated power / frequency | 16KW; 50Hz / 60Hz |
| Power stages | 500W、500W、1KW、2KW、4KW、4KW、4KW |
| Power factor / resistance tolerance | 1; ≤ 5% |
| Control supply | AC220V |
| Load input | 8 rear C14 sockets in A/B/C/D groups; each rated 10A |
| Wiring requirements | Both sockets in each group must connect to the same phase; branch A must be powered |
| Supplied power cords | As specified in the contract |
| Operating environment / temperature protection | Indoor; below 70℃ (protection temperature) |
| Protection and interlock | Short-circuit protection; overtemperature audible and visual alarm and unloading; loading disabled until the fan starts; manual reset after power-off |
| Cooling / airflow | Forced air cooling, front intake and rear exhaust; 2000 m ³ /h |
| Fan information | DC24V, 20060 |
| Resistor / internal wiring | Alloy resistors; silicone cable rated above 120℃ |
| Enclosure dimensions | Width×height×depth = 430 × 266 × 550 mm; bent and welded steel sheet with electrostatic surface coating |
| Weight | 15KG |
Applications and selection
- For AC220V / AC240V systems and simulated loads below 16KW, to check precision air conditioning, monitoring, power supply, UPS, diesel generation, racks and PDU under load.
- Test the load capacity and wiring reliability of AC distribution equipment, diesel generators, UPS, row distribution cabinets and PDU.
- Simulate load heating to check precision air-conditioning operation.
- Test UPS battery supply duration under load and diesel-generator starting and supply under load.