INLANX
Nederlands

Geen klantenaccount nodig. Gebruik gastformulieren voor vragen en sample-aanvragen.

Productcentrum
‹

RELIABLE BY DESIGN

ENS-1105C

Merk:INLANX

Beschrijving: De ENS-1105C acculader ondersteunt het onderhoud van accu's en UPS-systemen met laden in drie fasen en procesbewaking. Laadspanning: 90–145 VDC; laadstroom: 0–50 A.

Totale voorraad:100

Grootte
500*260*275 mm
Laadspanning
90–145 VDC
Laadstroom
0–50 A
Serie
ENS-1105C acculader
Merk
INLANX

Beschrijving: De ENS-1105C acculader ondersteunt het onderhoud van accu's en UPS-systemen met laden in drie fasen en procesbewaking. Laadspanning: 90–145 VDC; laadstroom: 0–50 A.

Totale voorraad:100

Merk:INLANX

Productgegevens

Productbeschrijving

Provides automatic charging, process monitoring and data analysis for battery and UPS power supply maintenance. Supports three-stage charging: constant current, constant voltage with decreasing current, and trickle float charging; records voltage, current, time and capacity. Suitable for charging and maintenance of lead-acid and lithium batteries; operating parameters must be set according to battery requirements.

Technische kenmerken

  • Three-stage charging: constant current → constant voltage with decreasing current (equalization at regulated voltage) → trickle float charging. Automatically controls charging for lead-acid batteries, lithium batteries and UPS power supply maintenance.
  • Automatic termination: stops charging when battery-bank terminal voltage or cell voltage reaches the set upper limit, charging time reaches its set value, or charging capacity reaches its set value; records continuous process data.
  • Touch operation: 7-inch high-brightness TFT LCD with a resistive touchscreen and 1024×600 resolution, supporting direct on-screen operation.
  • Wireless cell monitoring (optional): LoRa modules support 2V, 4V, 6V and 12V cells; each module monitors 6 cells simultaneously. The documentation example uses 4 modules for a 48V battery bank.
  • Wireless frequency bands: supports receiving and changing the wireless cell monitoring module's frequency band, with bands 1-10 available for multiple instruments in the same equipment room.
  • Cell analysis: with a cell acquisition unit installed, displays real-time charging cell-voltage bar charts and data tables, and identifies the cells with the highest and lowest voltages.
  • Historical curves: recorded battery-bank voltage and current curves can be reviewed.
  • Charging templates: 6 built-in test templates can be modified and recalled.
  • Data management: supports USB-drive data transfer, PC software analysis and report generation; test data names can be edited on the main unit.
  • Test resumption after power failure: enabled by default. Automatically restores the test state before the outage when mains power returns, maintaining continuous test records.
  • Online monitoring (optional): requires cell modules and a current clamp; monitors and records battery-bank voltage, current, capacity and time, and can generate reports.
  • Reserved interfaces: the RS485 master interface collects cell voltages, the RS485 slave interface provides remote control, and the CAN interface reads signal inputs. Actual interface availability is subject to the technical specifications.

Modellentabel

ModelDimensions (mm)
ENS-1105C500 × 260 × 275

Technische specificaties

Charging voltage90-145 VDC
Charging current0-50 A
Main unit weight≤15 kg
AC inputAC 380 V (ABCN+PE), 40-60 Hz
Main unit operationTouchscreen
Display7-inch TFT LCD, resistive touch, 1024×600
Data communicationRS485×1 (disabled by default)
Internal storage8 Gbit FLASH
Voltage measurement accuracy±0.5%FS + 0.1 V
Current measurement accuracy±1%FS + 0.1 A
Bank voltage display accuracy0.1 V
Bank current display accuracy0.01 A
Main unit protectionShutdown on overtemperature, overcurrent or uncontrolled current
Shutdown actuatorHigh-voltage DC switch
Reverse polarity protectionSupported
Abnormal condition protectionPower cord disconnection, main cable disconnection
Overtemperature thresholdResistor box 85°C; heatsink 100°C
AlarmLCD indication and buzzer
Withstand voltage test2200VDC, 1min. AC input-case; for DC endpoints, the source lists both "input-output" and "input-case", pending confirmation.
CoolingForced-air cooling
Operating temperature-5 to +50°C
Storage temperature-40 to +70°C
Relative humidity0-90% RH (40±2°C)
Rated altitude2000 m

Toepassingen en selectie

  • Suitable for charging and maintenance of lead-acid and lithium batteries; operating parameters must be set according to battery requirements.