12KW-AC/DC-PTC rack-mounted AC/DC PTC load bank
12KW-AC/DC-PTC rack-mounted AC/DC PTC load bank
RELIABLE BY DESIGN
12KW-AC/DC-PTC rack-mounted AC/DC PTC load bank
Brand: INLANX
Description: INLANX-12KW-AC/DC-PTC rack-mounted AC/DC PTC load bank is a high-power density rack-mounted test load equipment specially designed and developed for the 19-inch standard cabinet environment of IDC data center. 1KW, 1KW, 2KW, 4KW, 4KW loading in batches
Resistance, power rating, tolerance, TCR, package, lead length, mounting method, and labeling and packaging can all be customized.
Product series across the site can serve as alternatives to EBG, HVR, Vishay and other brands. Customers must verify samples and specifications before using replacement models in volume.
- Size
- 440*178*600 mm
- Rated power
- 12000 W
- Tolerance
- ±10%
- TCR
- 250-400ppm℃
- Series
- 12KW-AC/DC-PTC rack-mounted AC/DC PTC load bank
- Brand
- INLANX
Product details
Product description
Our 12KW-AC/DC-PTC rack-mounted load bank is a high-power-density test load developed specifically for standard 19-inch cabinets in IDC data centers.
Technical features
- Uses PTC resistors that automatically reduce power as temperature rises; internal silicone cables have a temperature rating of ≥150℃.
- • Loading is disabled until the fan starts; at an internal cabinet temperature of 70℃, the load is removed and an audible and visual alarm activates.
- • After overtemperature, confirm power disconnection and reset manually; monitor throughout testing.
- • Disconnect the supply side before the load side when removing cables.
- • Secure all 6 input plugs; use indoors with personnel monitoring throughout testing.
Model table
| Model |
|---|
| 12KW-AC/DC-PTC |
Technical specifications
| AC voltage range | AC192-250V; approximately constant load power |
|---|---|
| DC voltage range | DC192-288V; approximately constant load power |
| Rated power | 12KW |
| Frequency / power factor | 50/60Hz (AC); power factor 1 |
| Power steps | 1KW、1KW、2KW、4KW、4KW |
| Load power deviation | +5% to +10% (positive deviation) |
| Input interfaces | 6 independent C14 sockets at the rear; each rated 10A |
| Power cord | C13-C14; configurable for the site PDU |
| Resistor / internal wiring | PTC; silicone cable rated ≥150℃ |
| Temperature protection | 70℃ inside enclosure; alarm and load disconnect |
| Other protection | Fan interlock, fuse for short circuit/overcurrent, DC contactor |
| Cooling / airflow | Forced-air cooling, front intake and rear exhaust; 1500 m ³ /h |
| Fan voltage | DC24V |
| Cabinet dimensions | Width×height×depth = 440 × 178 × 600 mm |
| Installation / weight | Indoor; 18KG |
| PTC power degradation | ≤ 5% within 1 year; ≤ 8% within 3 years |
Applications and selection
- Suitable for AC 220V and DC 270V systems to check operation under load of precision air conditioning, power and environment monitoring, distribution, UPS, diesel generation, row distribution cabinets and PDU supply systems.