120KW-AC380V-R high power AC load bank
120KW-AC380V-R high power AC load bank
RELIABLE BY DESIGN
120KW-AC380V-R high power AC load bank
Brand: INLANX
Description: INLANX-120KW-AC380V-R high-power AC load bank uses nickel-chromium alloy resistors, panel manual step loading and forced air cooling, which is suitable for power system load testing. Used to test the load capacity and other electrical performance of generators and UPS, providing a 120KW AC simulated load.
Resistance, power rating, tolerance, TCR, package, lead length, mounting method, and labeling and packaging can all be customized.
Product series across the site can serve as alternatives to EBG, HVR, Vishay and other brands. Customers must verify samples and specifications before using replacement models in volume.
- Size
- 650*1800*850 mm
- Rated power
- 120KW
- Tolerance
- ±10%
- TCR
- 400ppm℃
- Technology
- Nickel-chromium alloy
- Series
- 120KW-AC380V-R high power AC load bank
- Brand
- INLANX
Product details
Product description
Provides a 120KW simulated AC load to test generator and UPS load capacity and other electrical performance.
Technical features
- Nickel-chromium alloy resistors provide stable power; internal high-temperature silicone cables withstand temperatures above 120℃.
- Panel 1P switches manually select and combine power steps.
Model table
| Model |
|---|
| INLANX-120KW-AC380V-R |
Technical specifications
| Product | High-power AC load bank |
|---|---|
| Rated voltage | AC380V |
| Rated power | 120KW |
| Three-phase AC load steps | 3KW、6KW、6KW、15KW、3×30KW |
| Single-phase AC load steps | 1KW、2KW、2KW、5KW、10KW、10KW、10KW |
| Power factor | 1 |
| Load accuracy | ≤5% |
| Fan / control supply | AC220V |
| Load connection | Quick connector |
| Cabinet dimensions | Width 650 × height 1800 × depth 850 mm |
| Operating temperature | Below 70℃ (set protection temperature) |
| Cooling | Forced air, front intake / rear exhaust |
| Loading method | Manual control-panel switching (1P switches) |
| Resistor material | Nickel-chromium alloy |
| Temperature protection | 70℃ protection setting; audible and visual alarm on overheating |
| Operation notes | Start the fan before applying load. After unloading, continue running the fan for about 3 minutes; disconnect the source side before the load side. |
Applications and selection
- • Test the load capacity of distribution equipment, diesel generators, UPS, row distribution cabinets and PDU electrical chains.
- • Check UPS load transfer and supply duration, diesel generator starting under load and computer-room air-conditioning operation.